DN400 × DN300 | 10 MPa (16″ × 12″) Minimum-Flow Valve Delivery for a Power Plant Project in Shanxi, China

Project Overview
An automatic recirculation valve (ARV), also known as a pump protection valve or minimum-flow valve, supplied by VORNET has two DN400 flanged connections in the main flow path and a DN300 flanged bypass connection.
The valve is designed for boiler feedwater, cooling-water and condensate equipment in power-station service. Under normal demand, discharge flow continues through the main line; when demand falls, the bypass provides a minimum-flow return path.
Project Challenges
The delivery lead time was limited to just ten days.
Our Solution
- Rapidly prepare drawings to project requirements and order forged raw materials.
- Maintain an organized workflow and clear priorities when handling urgent orders.
- A mature supply chain is essential to meeting urgent delivery requirements.
| Valve Type | Pump protection valve / automatic recirculation valve |
|---|---|
| Size | DN400 × DN400 × DN300 |
| Pressure Rating | PN100 (10 MPa) |
| Body Material | F304 stainless steel |
| Connection | Flanged |
Quality Control & Surface Treatment
The workshop photographs document internal component machining and positioning, body and stem assembly, and the finished valve before export packing for the September 2026 shipment. The recorded design, flange and testing references are GB/T 12224, GB/T 9124.1 and GB/T 26480 respectively; inspection scope and acceptance depend on the approved purchase documents and ITP. F304 material compatibility for corrosive service must be reviewed against the actual fluid and temperature rather than inferred from the grade alone.
How does VORNET handle valve orders with short delivery lead times?
For cast valves, we first check whether suitable patterns are available. For forged valves, lead time depends on the valve type, size and pressure rating.
What is an automatic recirculation valve used for?
When the main process flow falls below the required level, it maintains minimum flow to protect the centrifugal pump, helping reduce cavitation, overheating and damage.
How does the valve maintain minimum flow?
The integrated check valve and bypass device automatically respond to main-flow conditions and open the bypass path when minimum flow is required.
What information is needed for a similar pump protection valve?
Send the pump datasheet or performance curve, required minimum flow, operating pressures, return-vessel pressure, fluid properties and connection requirements. See our automatic recirculation valve sizing information for the complete checklist.